RLC(Resistance/Inductance/Capacitance) test at 3.8 to 150kHz

Please find the images and contents below.

RLC(Resistance/Inductance/Capacitance) test results for 0.20mm x 1,500 strands and 0.20mm x 4,650 strands, XLPE x 2 layers

### Remarks

1. TABLE : RCL DATA of 0.2mm x 1,500 with XLPE
– 0.20mm x 1500 strand (47.124 sq mm)
– Sample Length : 41m (Conversion Length : 1km)
– Conductor resistance : 14.834mΩ/41m/6℃ = [234.5+T2(20℃)] ÷ [234.5+T1(6℃)] x R1(14.834) = 15.6975Ω/41m/20℃ = 382.8685Ω/km/20℃
– Insulated resistance : 262000㏁/41m/8℃ = 10742 ㏁/km
 

2. TABLE : RCL DATA of 0.2mm x 4,650 with XLPE
– 0.20mm x 4650 strand (146.08 sq mm)
– Sample Length : 37m (Conversion Length : 1km)
– Conductor resistance : 4.4972mΩ/37m/6℃ = [234.5+T2(20℃)] ÷ [234.5+T1(6℃)] x R1(4.4972) = 4.7589Ω/37m/20℃ = 139.9703Ω/km/20℃
– Insulated resistance : 262000㏁/37m/8℃ = 9694 ㏁/km
 

## This test referred to IEC 60085(Thermal evaluation and classification of electrical insulation.)